ABB AF400-30-11 Contactor (100-250 V AC/DC Coil, 400 A / 200 kW at 400 V)

This model is an ABB three-phase block contactor, type AF400-30-11, with a rated control voltage of 100-250 V (50/60 Hz and DC), a 1000 V main circuit and 400 A AC-3 rating, able to control 200 kW motors at 400 V, with 3NO main contacts plus 1NO+1NC auxiliary contacts, for motor starting, isolation, bypass and distribution switching.
online consultation

Product Details

I. Product Overview

This product is a three-phase block contactor, type AF400-30-11, order number 1SFL577001R7011 (catalogue type AF400-30-11-70), with a rated control circuit voltage of 100-250 V, common to 50/60 Hz AC and DC. The main circuit is rated 1000 V (IEC) / 600 V (UL); all three main poles are normally open, 1NO+1NC auxiliary contacts are pre-mounted, and main circuit bar terminals are fitted.

The range uses electronically controlled wide-coil AF technology, so the contactor picks up reliably across the wide 100-250 V control range, tolerates large control voltage variations, reduces panel energy consumption and keeps distinct operation on unstable networks; surge protection is built in, with no additional suppression needed. The block design can be extended with add-on auxiliary contact blocks and a wide range of accessories.

The model is intended for motor starting, isolation, bypass and distribution switching up to 1000 V; in AC-3 duty it controls 200 kW motors at 400 V, and in AC-1 duty it switches 600 A loads at 40 °C. Mechanical durability is 3 million operations, with gG 630 A fuses for short-circuit protection.

II. Specifications

 

Parameter Value
Type AF400-30-11
Order Number 1SFL577001R7011 (AF400-30-11-70)
Product Name Contactor (block type, three-pole)
Number of Poles 3P
Main Contacts 3NO
Auxiliary Contacts 1NO + 1NC (pre-mounted)
Rated Control Voltage Uc 100–250 V, 50 Hz / 60 Hz / DC
Coil Operating Limits 0.85–1.1 × Uc (at ≤70 °C)
Rated Operational Voltage 1000 V (IEC) / 600 V (UL)
Rated Frequency 50 / 60 Hz
Conventional Free-air Thermal Current Ith 600 A (40 °C, open)
AC-1 Rated Current 600 A (40 °C) / 500 A (55 °C) / 400 A (70 °C)
AC-3 Rated Current 400 A (220–500 V, 55 °C) / 350 A (690 V) / 155 A (1000 V)
AC-3 Rated Power 110 kW (220–240 V) / 200 kW (380–400 V) / 220 kW (415–440 V) / 250 kW (500 V) / 315 kW (690 V)
AC-3 Making Capacity 10 × Ie
AC-3 Breaking Capacity 8 × Ie
Short-Circuit Protection gG fuses 630 A
Rated Insulation Voltage Ui 1000 V (IEC) / 600 V (UL/CSA)
Rated Impulse Withstand Voltage Uimp Main circuit 8 kV
Short-time Withstand Current Icw 1 s 4400 A / 30 s 2500 A / 1 min 4600 A / 10 s 840 A / 15 min 3100 A
Mechanical Durability 3 million operations
Max. Switching Frequency Mechanical 300 cycles/h; AC-1, AC-3 300 cycles/h; AC-2/AC-4 60 cycles/h
Coil Consumption Pull-in 1155 V·A; holding 4.8 W (AC) / 4.5 W (DC)
Operate Time Energization to NO closing 50–120 ms; de-energization to NO opening 48–58 ms
Main Circuit Connection Bar 47 mm²; rigid Cu cable 240 mm² or 2×240 mm²; rigid Al cable 2×240 mm²
Main Terminal Torque 35 N·m
Degree of Protection Coil terminals IP20; main terminals IP00
Ambient Temperature -40 … +70 °C (with thermal O/L relay -25 … +50 °C)
Storage Temperature -40 … +70 °C
Max. Operating Altitude 3000 m without derating
Dimensions (W×D×H) 186 × 216 × 278 mm
Net Weight 10.6 kg

V. Model Description

AF400-30-11 is built from series, rating and contact configuration: AF denotes the wide-coil electronically controlled contactor series; 400 denotes the 400 A AC-3 rating class; 30 denotes three normally open main poles and no normally closed main pole; 11 denotes one normally open plus one normally closed pre-mounted auxiliary contact. The -70 suffix is the coil voltage code for 100-250 V 50/60 Hz and DC; other suffixes in the same series cover different control voltages (for example -69 for 48-130 V AC/DC), so the suffix must be verified and a different voltage version must not be substituted. Add-on auxiliary contact blocks and low voltage ride-through modules (RU19/120, RU19/240) are available for this model.

VI. Why Choose Us

  • Professional channel supply covering the full ABB AF contactor range
  • Strict quality inspection process ensuring reliable product quality
  • Professional engineering team providing technical support and selection verification
  • Quick response, efficient logistics, orders accepted
  • Quality assurance, worry-free after-sales service

VII. FAQ

Q1: What is the coil voltage?

A: Rated control voltage 100-250 V, common to 50/60 Hz AC and DC, operating limits 0.85–1.1 × Uc.

Q2: How much motor power can it control?

A: In AC-3 duty, 200 kW at 400 V, 220 kW at 440 V and 315 kW at 690 V.

Q3: How many auxiliary contacts are included?

A: 1NO+1NC pre-mounted, extendable with add-on auxiliary contact blocks.

Q4: How is short-circuit protection set up?

A: With gG 630 A fuses.