ABB AF400-30-11 Contactor (100-250 V AC/DC Coil, 400 A / 200 kW at 400 V)
I. Product Overview
This product is a three-phase block contactor, type AF400-30-11, order number 1SFL577001R7011 (catalogue type AF400-30-11-70), with a rated control circuit voltage of 100-250 V, common to 50/60 Hz AC and DC. The main circuit is rated 1000 V (IEC) / 600 V (UL); all three main poles are normally open, 1NO+1NC auxiliary contacts are pre-mounted, and main circuit bar terminals are fitted.
The range uses electronically controlled wide-coil AF technology, so the contactor picks up reliably across the wide 100-250 V control range, tolerates large control voltage variations, reduces panel energy consumption and keeps distinct operation on unstable networks; surge protection is built in, with no additional suppression needed. The block design can be extended with add-on auxiliary contact blocks and a wide range of accessories.
The model is intended for motor starting, isolation, bypass and distribution switching up to 1000 V; in AC-3 duty it controls 200 kW motors at 400 V, and in AC-1 duty it switches 600 A loads at 40 °C. Mechanical durability is 3 million operations, with gG 630 A fuses for short-circuit protection.
II. Specifications
| Parameter | Value |
|---|---|
| Type | AF400-30-11 |
| Order Number | 1SFL577001R7011 (AF400-30-11-70) |
| Product Name | Contactor (block type, three-pole) |
| Number of Poles | 3P |
| Main Contacts | 3NO |
| Auxiliary Contacts | 1NO + 1NC (pre-mounted) |
| Rated Control Voltage Uc | 100–250 V, 50 Hz / 60 Hz / DC |
| Coil Operating Limits | 0.85–1.1 × Uc (at ≤70 °C) |
| Rated Operational Voltage | 1000 V (IEC) / 600 V (UL) |
| Rated Frequency | 50 / 60 Hz |
| Conventional Free-air Thermal Current Ith | 600 A (40 °C, open) |
| AC-1 Rated Current | 600 A (40 °C) / 500 A (55 °C) / 400 A (70 °C) |
| AC-3 Rated Current | 400 A (220–500 V, 55 °C) / 350 A (690 V) / 155 A (1000 V) |
| AC-3 Rated Power | 110 kW (220–240 V) / 200 kW (380–400 V) / 220 kW (415–440 V) / 250 kW (500 V) / 315 kW (690 V) |
| AC-3 Making Capacity | 10 × Ie |
| AC-3 Breaking Capacity | 8 × Ie |
| Short-Circuit Protection | gG fuses 630 A |
| Rated Insulation Voltage Ui | 1000 V (IEC) / 600 V (UL/CSA) |
| Rated Impulse Withstand Voltage Uimp | Main circuit 8 kV |
| Short-time Withstand Current Icw | 1 s 4400 A / 30 s 2500 A / 1 min 4600 A / 10 s 840 A / 15 min 3100 A |
| Mechanical Durability | 3 million operations |
| Max. Switching Frequency | Mechanical 300 cycles/h; AC-1, AC-3 300 cycles/h; AC-2/AC-4 60 cycles/h |
| Coil Consumption | Pull-in 1155 V·A; holding 4.8 W (AC) / 4.5 W (DC) |
| Operate Time | Energization to NO closing 50–120 ms; de-energization to NO opening 48–58 ms |
| Main Circuit Connection | Bar 47 mm²; rigid Cu cable 240 mm² or 2×240 mm²; rigid Al cable 2×240 mm² |
| Main Terminal Torque | 35 N·m |
| Degree of Protection | Coil terminals IP20; main terminals IP00 |
| Ambient Temperature | -40 … +70 °C (with thermal O/L relay -25 … +50 °C) |
| Storage Temperature | -40 … +70 °C |
| Max. Operating Altitude | 3000 m without derating |
| Dimensions (W×D×H) | 186 × 216 × 278 mm |
| Net Weight | 10.6 kg |
V. Model Description
AF400-30-11 is built from series, rating and contact configuration: AF denotes the wide-coil electronically controlled contactor series; 400 denotes the 400 A AC-3 rating class; 30 denotes three normally open main poles and no normally closed main pole; 11 denotes one normally open plus one normally closed pre-mounted auxiliary contact. The -70 suffix is the coil voltage code for 100-250 V 50/60 Hz and DC; other suffixes in the same series cover different control voltages (for example -69 for 48-130 V AC/DC), so the suffix must be verified and a different voltage version must not be substituted. Add-on auxiliary contact blocks and low voltage ride-through modules (RU19/120, RU19/240) are available for this model.
VI. Why Choose Us
- Professional channel supply covering the full ABB AF contactor range
- Strict quality inspection process ensuring reliable product quality
- Professional engineering team providing technical support and selection verification
- Quick response, efficient logistics, orders accepted
- Quality assurance, worry-free after-sales service
VII. FAQ
Q1: What is the coil voltage?
A: Rated control voltage 100-250 V, common to 50/60 Hz AC and DC, operating limits 0.85–1.1 × Uc.
Q2: How much motor power can it control?
A: In AC-3 duty, 200 kW at 400 V, 220 kW at 440 V and 315 kW at 690 V.
Q3: How many auxiliary contacts are included?
A: 1NO+1NC pre-mounted, extendable with add-on auxiliary contact blocks.
Q4: How is short-circuit protection set up?
A: With gG 630 A fuses.